16
CONFIGURATION USING HART
®
I
MPORTANT
:
The digital HART
®
c
ommunication is superimposed on the
4-20 mA loop and requires a min. load resistance of 250 Ω and a max load
resistance of 450 Ω.
Junction
Control
Room
Display
Power
Supply
Current
Meter
250 Ω < R
L
< 450 Ω
CONNECTIONS
CHECK HART
®
Connection of your Hart communicator:
• at power terminals (+) and (-) in wiring compartment
• at first junction box between unit and control room.
Before starting the HART
®
configuration procedure – check if your HART
®
commu-
n
icator is equipped with the proper Jupiter Device Descriptors (DD’s).
I/O start up the communicator
Select NO: go offline
Select 4: utility
Select 5: simulation
Check manufacturer: Magnetrol
HART MENU
I/O Start up the device
1 Enter Device Set Up «
DEVICE SET UP»
Press one of the following alphanumeric keys (if no key is sensed after 8 s, the
unit will automatically jump to RUN mode and alternatively show Level/% Output
and Loop signal
1 for entering Calibration «
CALIBRATION» (see page 11 for additional informa-
tion)
2 for entering Basic Set Up «
BASIC SET UP» – general HART
3 for Advanced Set Up «
ADVANCED SET UP» (see page 11 for additional infor-
mation)
4 for entering Diagnostics «
DIAGNOSTICS» (see page 11 for additional infor-
mation)
5 for entering Review «
REVIEW» to review all settings.
When the proper software version is not found, consult your local HART
®
Service
Center to load the correct Jupiter DD’s.
HCF Release Date
HART Version Compatible with software
July 2003
Dev V2 DD V1 Version 2.0A ... 2.0B
July 2006
Dev V3 DD V2 Version 3.0A and later
HART ERROR MESSAGES
For easy PACTware set up, consult
instruction manual 59-600
LCD Class HART
Status
SIL1 SIL2 Description
TrimReqd
Warning Yes Yes Yes Loop DAC trim values are defaults, loop output
inaccurate
Cal Reqd
Warning Yes Yes Yes Default calibration parameters in use, level reading
inaccurate
Lo Temp
Warning Yes Yes Yes Present temperature in electronics compartment is
below -40 °C
Hi Temp
W
arning
Y
es
Y
es
Y
es
Present temperature in electronics compartment is
above +80 °C
Float 2
Fail
Fault Y
es
Y
es
Y
es
No level signal detected from Float 2
Float 1
Fail
Fault Y
es
Y
es
Y
es
No level signal detected from Float 1
No Signal
Fault Yes Yes Yes No level signal detected from any float
LoopFail
Fault Yes Yes Yes Loop current differs from the commanded value
Snsr Brd
Fail
Fault Yes Yes Yes Invalid reading from the Analog Board
DfltParm
Fault Y
es
Y
es
Y
es
Non-volatile parameters have been defaulted